PROLINE ZI INTERFACE UNITS
ZI-01/ZI-01RS

2,000 Metres TH sensor cable connection per interface unit
Colour coded LCD Display
Alarm Point Location
Volt-free output contacts FIRE and FAULT
RS 232 serial link (ZI-01RS only)
2 part terminals ease of wiring
50 ohms max: interconnecting cable
IP 65 rated enclosure
Integrated with ALL central Fire & Alarm & Building Management Control Panels
Multi-zone units available
Hazardous Area applications Safe area Installation
ZI-01/RS SPECIFICATIONS
Nominal 24 Vdc dedicated supply or Central panel address loop powered (12-36 Vdc range)
Quiescent Current: max. 7mA
Alarm Current: max. 40mA
TH sensor monitoring: 3mA @ 1V
EMC and EMI surge protection
Alarm point location display metric or Imperial
Solid state volt free contacts fire & Fault:25 ohms/Max 60 vdc/100ma
Fault monitoring N/C contacts or N/0-C-N/C to be specified on order
Over Current/Voltage Protected
EN61000-6-2/3 Tested
Ambient Installation range: to+70C
Humidity: 95%
Enclosure size: 180 x 180 x 60mms (7 x 7 x 2.5 inches)
Unit Weight: 3 kgs.
OPTIONS
ZI-01RS-4 (4 ZONE) and ZI-01RS-8 (8 Zone) Versions of the above are available for single enclosure mounting with multiple cut outs for LCD Display viewing.
Quiescent Current (4 zone): 112mA
Quiescent Current (8 zone): 224mA
Alarm Current: 40mA
Enclosure dimensions:- ZI-01RS-4
. 300 x 300 x 132mms ZI-01RS-8
. 600 x 300 x 132mms
ZI-03

site programmable
FEATURES
5,000 Metres TH sensor cable connection per interface unit
Colour coded LCD Display
Alarm Point Location
Site Programmable
50 Additional alarm outputs option
Sub-zone boundary fire location Overlaps
50 ohms max: interconnecting cable
IP 65 rated enclosure
Output signaling volt free contacts FIRE and FAULT and RS 232 link
Integrated with ALL central Fire Alarm & Building Management Control Panels
Hazardous Area applications safe area Installation of interface unit
ZI-03 SPECIFICATIONS
Nominal 24 Vdc dedicated supply (18-36Vdc range)
Quiescent Current: max. 28mA
Alarm Current: 40mA
TH sensor monitoring: 3mA @ 1V
EMC and EMI surge protection
Alarm Point location display - metric
Output Relays Solid state 60V load Voltage/100 mA load current
Faullt monitoring N/C contacts or N/O-C-N/C to be specified on order
Over Current/Voltage Protected
EN61000-6 2/3 Tested
Ambient Installation range: to + 70C
Humidity: 95%
Enclosure size: 255 x 180 x 63mms (10 x7 x 2.5 inches)
Unit Weight: 5 kgs
OPTIONS
ZI-03 BASE UNIT PROVIDES COMMON FIRE & FAULT OUPUTS PLUS 10 ADDITIONAL SITE PROGRAMMABLE OUTPUTS.
4 x ZI-03R EXTENSION UNITS (10 OUTPUTS PER ENCLOSURE) CAN BE PURCHASED TO ACHIEVE MAXIMUM 5O PROGRAMMABLE OUTPUTS
ZI-05
PHOTO AVAILABLE SOON 
site programmable
FEATURES
128,000 Metres TH sensor cable connection capability each ZI-05
Multiple alarm condition signaling
Individual zone alarm point
Alarm Point Location
Site Programmable
Location display incl: multi alarms
64 zone boxes per ZI-05
2,000 metres TH sensor cable per zone box
Loop wired configuration
20 kms power/signal wire loop
Overheat/Fire AND Ambient Temperature Monitoring & Signaling
Continued detection in Fault mode
One alarm will not inhibit receipt of Additional alarm signals at the ZI-05
Open & short circuit fault signaling Central panel (supplied by others)
ZI-05 SPECIFICATIONS
FULL SPECIFICATION TO BE RELEASED AT DECEMBER 2007 OFFICIAL MARKET INTRODUCTION IN DUBAI , U.A.E.