Jointing/Terminal Boxes
On site installation of PROLINE digital linear heat sensor cables will involve at least one of the following wiring connections:
A) Sensor cable to Sensor cable: For............
i) existing installation length extensions,
ii) sectional replacements/repairs
iii) to achieve multiple alarm temperatures on a single zone by jointing cables with different alarm temperature ratings.
B) Sensor cable to Short term fire-proof interconnecting cabling
Where interface units are installed “remote” from the risk area
C) Remote end termination of sensor cable
Termination box fitted with end of line resistor for open circuit fault condition monitoring.
With Junction boxes remaining the most reliable and most commonly end user specified method for sensor cable joints and / or end of line terminations,PROLINE has researched a number of manufacturers of such boxes-suitable for Industrial risk applications, and offers the following units – based upon quality and price.
Heavy Duty Industrial Unit - Type...A 804-407
Photographs below are not to scale; gland image enlarged for increased detail

The A804-407 junction /termination box is manufactured from polystyrene, and is highly resistant to animal and vegetable fats, mineral oil, deisel, weak acids, strong and weak alkaline solutions and alcohol.
Dimensions: 93 x 93 x 55 mms Temperature range: -40C to +70C continuous ( +80C short term exposure) Rating: IP65 Flame Protection: glow wire test 750C to EN 60695-2-11 Cable entry: Compression glands or use of 8 elastic self sealing membranes Terminal/poles: 4mm2. Fixing: Mounting clip for snap on fixing or 4 internal openings outside of sealing area. Cover: 4 captive quick release screws. Colour; RAL 7035 light Grey
Glands supplied with box: M16 and M20 compression type with lock nuts.
EExe Hazardous Area Unit - Type 500-404

The type 500-404 hazardous area installation In line jointing and end of line termination boxes are manufactured according to E DIN IEC 60998-2-5, U i, = 400v, black for EX protection zones 2 and 22, authorisation number TUV 05 ATEX 7200, Empty housing TUV 03 ATEX 7015 U, weather proof, shock resistant and halogen free, Only authorised with KVR EX screw fittings.
Dimensions: 93 x 93 x 55 mms (3.7 x 3.7 x 2.2 inches) Internal Mounting: Approved EExe Terminals – II 2GD Eexe II Certification no: Nemko03ATEX020U Cable Glands: Type 227-520 Approved glands only IP rating: IP65 T 60 Material: Re-Inforced Polycarbonate Colour: Black Hazardous Area Classification: Eex II 3GD Eex nA II T6 Compliance Code/s : EN 60079-15 : 2003 EN 50281-1-1 : 1998 Certification Nos. TUV 03 ATEX 7015 U , TUV 05 ATEX 7200 Operating Temperature Range: -30C to +70C
The information provided on this data sheet is accurate at time of going to print. In the interest of improving quality and design Proline Protection Systems Ltd reserve the right to amend specifications without prior notice.
Registered Office – KingsWorthy Court , Court Road , KingsWorthy, Winchester, Hampshire SO23 7QA U. K. Registered in England - Number 4421495 V.A.T. Registration Number – GB 799 9244 45 |