“Nero” Water Detection System

Air conditioning, sprinkler systems, water cooled processors and heating systems are all potential sources of water leakage which if undetected can seriously damage today's complex electrical, communication and computer networks; even a small leak can prove disastrous
Features
Auxiliary alarm contacts Monitored alarm outputs
Fully monitored – open & short circuits
Zonal repeat contacts
Easy to install
Easy to service and maintain
Bright dual LEDs
Clean low profile appearance
Diagnostic fault LEDs
Lockable enclosure
Special colours and finishes available
Product Overview
The “Nero” Water Detection System installed in vulnerable areas will continuously monitor the potential hazards- 24/7.
The system has the facility for 24 hour battery standby in the event of power failures.
The system has an attractive and unobtrusive control panel containing the alarm circuitry and power supply. Connection to the control panel via a simple two core leader cable of the recoverable moisture sensitive cable or point type localised detection probe provides rapid and cost effective installation. Upon detection of a leak, the green alarm lamp on the control panel willflash accompanied by a warning buzzer. The alarm may be extended to a remote location by extension sounder/indicator units. Disconnection of a moisture detection probe or break in the “Nero” moisture sensing cable is immediately indicated on the control panel by the yellow line fault indicator. This ensures that the integrity of the system cannot be compromised without a warning.
Floor Mounting Probe - PR2101
This adjustable height probe is simply screwed into the floor and adjusted to give the required detection level. An LED indicator on the top of the probe gives a clear indication of which probe has been activated and this may be extended to a remote lamp location (e.g. above false floor level) using a remote indicator. The probe is connected to the control panel wiring via a flexible cable which plugs into the probe. This plug connection is monitored by theline fault circuit of the control panel.
Drip Tray Mounting Probe -PR2102
This probe has exactly the same facilities as the floor mounting probe but has a bracket for mounting onto the side of an air conditioning unit drip tray. The probe is then adjusted to give the required detection level and plugged into the detection circuit.
“Nero” Moisture Sensing Cable
Available as either standard 5 metres,10 metres or custom designed lengths, “Nero” is a flexible cable which will continuously monitor large areas. When even a small amount of water comes into contact with the sensing cable it is absorbed by capillary action thereby triggering an alarm.
After the source of the leak has been removed, “Nero” will dry out in around 20 minutes for use again.
Unplugging or cutting the “Nero” cable will be immediately Indicated on the control panel by the line fault indicator.
Longer runs can be made by simply plugging lengths of “Nero” together. Special lengths can be made to order.
Each zone requires a junction box and an end of line DIN plug.
Model P2004001 Model No. P2002000
Model N2106 connection box and an end of line DIN plug.
Technical
Specifications common to ABS & Metal Control Panels
Sounder outputs -2 outputs each rated at 500mA
Isolatable remote contact -volt free changeover 1 Amp at 30V DC fused at 500mA
Auxiliary alarm contact -volt free changeover 1 Amp at 30V DC
Sounder fuses -500mA each
System fuse -2 Amp
Mains input -230V AC
ABS Enclosure, 1, 2, 4 & 6 Zones
Size -315W x 235H x 84D
Construction -flame retardant ABS injection
Power supply -1.25 Amp
Battery capacity -7.0A/h 24 hour standby 2.8A/h
Max. battery capacity 7.0A/h
Finish light texture
Standard colour stone grey
Metal Enclosure - 2, 4, 8, 12, 16 & 24 Zones
Construction -zone 1.2mm fully welded sheet steel
Finish -epoxy powder coat
Standard colour -2 tone grey
2 & 4 zone size -365W x 290H x 88mmD
8 & 12 zone size -500W x 355H x 107mmD
16 & 24 zone size -570W x 420H x 110mmD
Power supply -1.25 Amp (2, 4 & 8 zone)
2.5 Amp (12, 16 & 24 zone)
Max. battery capacity -4.0A/h (2 & 4 zone)
6.0A/h (8 zone)
7.0A/h (12 zone)
12.0A/h (16 & 24 zone)
230V AC
Technical – Localised Detection Probes
Size -95mm (max.) 80mm (min.) H x 45mmD x 100mmW
Indicator -green LED
Connection -4 pin din flying lead (1 metre)
Material -black nylon
Guidelines – Localised Detection Probe:
Maximum recommended coverage: -20sq metres per detector
Maximum recommended detectors per zone: -20
Maximum distance between probes for perimeter detection: -3 metres
Sensor height above finished floor: - 1mm to 3mm
Leader cable: -0.5mm round 3A
Guidelines- “Nero” Cable:
Maximum recommended length per zone: -50metres
Recommended pitch between cable for area protection: -2metres
Minimum bend radius: -150mms
Equipment
Product code Description Weight
P2001000 Single zone control panel (ABS) 3.5 kgs
P2002001 2 zone control panel (metal) 5.0 kgs
P2002000 2 zone control panel (ABS) 3.5 kgs
P2004001 4 zone control panel (metal) 5.1 kgs
P2004000 4 zone control panel (ABS) 3.5 kgs
P2006000 6 zone control panel (ABS) 3.5 kgs
P2008003 8 zone control panel (metal) 8.4 kgs
P2012003 12 zone control panel (metal) 8.6 kgs
PR2101 Floor mounted probe -
PR2102 Drip tray probe -
RI2103 Remote indicator -
N2104 5 metres “Nero” Moisture Sensitive Cable -
N2105 10metres “Nero” Moisture Sensitive Cable -
N2106 “Nero” junction box -
N2110 End of line plug -
N2111 Leader cable 50M -
N2112 Fixing clips (100) -
S 9615/A Protection Cage for Floor Mounted Probe -
F/A/1W Fire-Cryer® with water leakage alarm -
Larger control panels are available on request
The manufacturer reserves the right to amend specifications without prior notice