Interface Unit - ZI-03

 

 

 

 

 

 

 

 

 

The  ZI-03 interface monitors up to 5000 metres / 16,400 ft of Proline TH digital linear temperature sensing cable plus 50 ohms (maximum resistance) of interconnecting cable - where required.  Its development considers the potential for multiple extinguishing, ventilation, smoke extraction zones of operation within a single detection zone covered by the 5000m of Proline "TH" sensor cable and the preference for restricting extinguishing etc to the area in alarm only - thereby reducing costs associated with gaseous discharge and/or clean up of water based extinguishants.

A site programming facility allows sections of the sensor cable to be dedicated to 1 of up to 50 alarm outputs - allowing the customer control panel to identify which associated zone/s of extinguishing etc should be operated.  Minimum "sub-zone" length of sensor cable which may be programmed is 100 metres.

For areas where no dedicated alarm signal is required - as in transfer points from 1 floor or room to another - this length of sensor cable can be programmed as a "dead" zone - i.e. not dedicated to any specific alarm output.

 

 

FEATURES

 Single sensor cable line monitoring
900ohms Proline type “TH” digital sensor cable
Alarm Point Location
Displayed in metres
Site programmable via customer laptop computer
Windows XP, Windows 2000 or Vista
Maximum 50 Additional Programmable alarm outputs
No minimum length restriction
Back lit internal LCD display
Green=Normal, Flashing Green=Fault, Red=Alarm
Solid-state volt-free contact outputs
Alarm and Fault
2 part terminal blocks
For Ease of wire connection in restricted locations
Where Interconnecting cable is used
max. 50 Ohms resistance
IP65 rated enclosure
NEMA 4X equivalent
Powered from dedicated 24VDC supply
supplied by others
RS232 serial interface
provides ASCII data to external device.
Conforms to EN50020 2002 AND EN60079
11 2006 for associated sensor cable operation
Certificate MTL02ATEX7700CX
ATEX II3 GD when used with MTL 7758+ zener barrier ZI-03

 

 

SPECIFICATIONS: ELECTRICAL & ENVIRONMENTAL

Power Supply
Monitored nominal 24vdc (18vdc - 36vdc range)
Quiescent Current
28mA @24vdc
Alarm Current
40mA @24vdc
Monitoring Current on associated TH sensor cable
3mA @1v
On board surge /transient / EMC & EMI protection
Yes
Tested to EN61000-6-2 and 61000-6-3
For Emissions and Immunity
Alarm Point Location
In Metres only
Output relays
60V load voltage / 100mA load current
Over current / voltage protected
Yes
Recommended Ambient temperature Installation limits
0C to +70C
Humidity
Maximum 95%
Enclosure Dimensions
254(H) x 180(W) x 63(D) mms
Gross Unit Weight - ZI-03 Base unit only
3kgs



The ZI-03 is supplied - as standard - with common ALARM and common FAULT outputs, RS232 serial link and 10 (ten) programmable alarm outputs. Where more are required, up to 4 x ZI-03R extension units may be added - each of which provides 10 additional programmable outputs. See figure 4 below for connection information. 

 

 

 

 