Linear Heat Detection

 

 

SharpEye™ 20/20U-UB UV Flame Detector

                                              

                                                                 

 

TThe SharpEye UV Optical Flame Detectors 20/20U and 20/20UB (which includes a BIT function) are designed to meet the strict
industry performance requirements. The UV sensor has been carefully selected to ensure the greatest degree of spectral matching to the radiant energy emissions of fire. Flame is detected typically within 3 sec. for a 1ft.2 (0.1m2) pan gasoline fire. A unique Fast UV Flame Detector Model (20/20FU) detects within several milliseconds a saturated UV signal caused by an
explosion or a large fire.
The microprocessor design allows for unique field programmability making these flame detectors easily adaptable to all environments, applications and requirements.
The SharpEye UV Flame Detector incorporates a special logic circuit that helps prevent false alarms caused by solar radiation.
Both U and UB models are self-contained, optical flame detectors that function as stand-alone units directly connected to external devices such as alarm systems or automatic fire extinguishing systems.
The UV detectors are particularly useful for detection of invisible flames from fuels such as: Hydrogen, Hydrides, Ammonia, Silane and other inorganic fuels.

* It is important to note that this detector must not be exposed to UV radiation sources such as: electrical arcs, sparks and welding, etc

Main Features


• UV Spectrum Design                                                                                       •  4-20mA source (3-4 wires) configuration

• Typical 3 second Response                                                                          •  MTBF Minimum 100,000 Hours

 • User Programmable Configuration                                                             •  3-Year Warranty

 • Automatic and Manual Built-In-Test (BIT) - UB                                          • FM, CSA, ATEX/Cenelec Approved                                          

 • Standard 4-wire Connection                                                          

Applications


• Aerospace Industry - Hydroxy, Hydrogen and Hydrazine fuels                • Pharmaceutical Industry

• Automotive - manufacturing, paint spray booths                                        • Polymers,Solvents and Glue - manufacturing and curing 

• Chemical Industry - production, storage, transportation                          • Power Generation Facilities - pump areas, generator 
                                                                                                                                  rooms, unmanned stations, gas-fired and 
• Explosives & Munitions - handling and storage                                           coal fired reactors

• Paint - manufacturing facilities                                                                      • Printing Industry - solvent handling, presses,
                                                                                                                                      drying processes

•  Petrochemicals - production, storage, shipping facilities                       • Warehouses - storage facilities for flammable
                                                                                                                                       materials
 

 

General Specifications

Spectral Response :          UV: 0.185 - 0.260 microns. 
                                               

Detection Range                 Gasoline fire at 50 ft (15m)                                       JP4 fire at 37 ft (11m)
                                                N-Heptane fire at 50 ft (15m)                                    Kerosene fire at 37 ft (11m)
                                                Alcohol 95% fire at 37 ft (11m)                                 Methane* fire at 30 ft (9m)
                                                Diesel Fuel fire at 37 ft (11m)                                   Propane* fire at 30ft (9m)
                                                                                                                                                * 0.5m plume fire
Response Time                  Typical 3 sec.

Adjustable Time Delay       Up to 30 sec. (up to 20 sec. in compliance with FM requirements)

Field of View                         90° horizontal, 90° vertical

 Built-in-Test                          Manual and Automatic BIT (in model 20/20UB only)

Temperature Range            Operating:                -40°F (-40°C) to 160°F (70°C)
                                                 Operating Option:   -40°F (-40°C) to 185°F (85°C) 
                                                 Storage:                    -65°F (-55°C) to 185°F (85°C)

Humidity                                 Up to 95%

 

Electrical Specifications 

 Power Supply                       Operating Voltage:18-32 VDC

 Power Consumption           Max.    80mA in stand-by
                                                  Max. 120mA in alarm

 Electrical Connection          2 x 3/4" - 14NPT conduits
                                                  or 2 x M25 x 1.5 mm ISO

 Electrical Input Protection:   According to MIL-STD-1275A

Electromagnetic Compatibility :    EMI/RFI protected CE Marked

 

Outputs

 Relays                                    Alarm                              - 2A at 30 VDC, 0.5A at 250 VAC
                                                  Fault and Accessory    - 5A at 30 VDC and 250 VAC
                                                  Fault relay normally closed, others normally open

 4-20mA                                  Source configuration
                                                  Fault: 0 +0.5mA 
                                                  BIT Fault: 2mA ±10%
                                                  Normal: 4mA ±5% 
                                                  Warning: 16mA ±5%
                                                  Alarm: 20mA ±5%
                                                  Resistance Loop: 100-600 Ohms.

 Mechanical Specifications

Dimensions                            4.7" x 5.2" x 5.2" (120 x 132 x 132 mm)

 Weight                                     Aluminum: 8.1Lb (3.7 Kg)
                                                  St.St 316L: 14.3Lb (6.5 Kg)

 Enclosure                               Aluminum, heavy-duty copper free (less than 1%), white epoxy enamel finish. 
                                                  Optional - Stainless Steel 316L with electro polish finish.

Environmental Standards    Meets MIL-STD-810C for Humidity, Salt & Fog, Vibration, Mechanical Shock, High Temp, Low Temp 

Water and Dust                      IP66 and IP67 per En60529 
                                                  NEMA 250 6P 

 

Hazardous Area approvals

ATEX / Cenelec                     EX II 2G, EExd IIB + H2 T5 (70°C) ,T4 (85°C)
                                                 EX II 2G, EExde IIB + H2 T5 (70°C)

FM / CSA                                 Class I Div. 1, Groups B, C & D 
                                                 Class II Div. 1, Groups E, F & G

Accessories

Fire Simulator                       20/20-311

Swivel Mount                         20/20-003 (St. St. 316L)

 

Specifications subject to changes
For more information view manual or website www.spectrex-inc.com
DS-F-UV, November 2003 

 

 

 

 The information provided on this data sheet is accurate at time of going to print. 

 In the interest of improving quality and design Proline Protection Systems Ltd reserve the right

 to amend specifications without prior notice.


               
Registered Office:KingsWorthy Court, Court Road, KingsWorthy, Winchester,Hampshire SO23 7QA   U. K.
Registered in England - Number  4421495         V.A.T. Registration Number – GB 799 9244 45


 

About Contact Send us an Enquiry Linear Heat Detection General Linear Heat Detection Products Linear Heat - Fixings/Supports Linear Heat - Junction Boxes Linear Heat Detection Applications Linear Detection - Design Newsheets Consultant Specification FAQ's Product Approvals Speciality Cables Beam Detectors Flame Detectors Aspirated Smoke Detector Moisture Detection Stop Press Terms and Conditions Payment Terms