PROLINE  - TYPE IH-153E  EMBER DETECTOR

 

 

Description

 

The IP67 rated model IH-153E Ember Detector employs Infra-red sensitive photoelectric sensors for the detection of glowing embers on applications such as COAL CONVEYORS. The unit has a narrow spectral sensitivity ( 3 to 5 um) making it impervious to visible light. The detector can reliably and rapidly detect weak Infra-Red radiation emissions from embers resulting from smouldering fragments of wood or coal. The sensitivity of the IH-153E, being designed and constructed specifically for the detection of glowing embers,  is far superior to more “conventional” flame detectors. With Instrument air air purging at 3 to 7 bar used to keep the detector “eye” clean in polluted environments.
The IH-153E will detect 100 sq cms glowing ember at a distance of 1 to 3 metres in a 90 degree cone angle and straight line.
Connection of the IH-153E to any standard Fire Alarm Control Panel, annunciator, PLC, DCS is by way of the potential free NO/NC contacts provided. Operating Status indication of the detector is by LED’s (flickering green = normal condition, static red = alarm).


Applications:


• Highly recommended for use on coal conveyors to detect smouldering coal or glowing embers on a moving belt.
• Any Material transportation system where glowing embers may present a risk of fires.
• Environments that are unsuitable for other types of detectors to be installed and operate with a moving ember or small flame fire risk


Detector Sensitivity:


• 100 sq cms at a distance of 1 to 3 metres in a 90 degree cone angle and straight line.


Advantages:


• Rugged construction for use in challenging environments
• High Sensitivity – even in Mist and Fog
• Easy to instal and operate
• High speed response
• Free from false alarms
• Visual operating status indication
• Low maintenance


Installation Considerations:


The fladet IH-153E detector must be installed ensuring there is no obstruction in its “line of sight”.
Other IR radiation sources (sunlight or hot bodies) may adverselt affect detector performance
For conveyor applications, detector mounting should be on the hood or gantry of the conveyor structure with detector line of sight along (not across) the conveyor belt.


Maintenance & Inspection:


For maximum sensitivity, the surface of the detector tube should be kept free from dirt or other contaminants at all times. Periodic testing of the detector –using controlled embers-should be carried out.
An additional provision exists for connection to a pneumatic air purging system to keep the detector surface clean.


Ordering Information:


a) IH-153E-FP…..For direct connection to conventional fire alarm panel -1 x fire relay contact output.
b) IH-153E-AP….For Addressable panel/Annunciation panel/PLC/DCS connection. Detector includes 1 x NO-COM-NC FireRelay, 1x NO-COM-NC Fault Relay + 1 x NO-COM-NC Auxiliary fire relay.


Optional Accessories:


a) 1H-323 Air Purging Unit – stand alone version. 1 required per ember detector. 230VAC operation. Remote control operation type available.
b) MB-01 Tilting Mounting Base


Technical Specification:


• Supply Voltage – 24VDC  +/- 20%
• Sensor – IR 3000-5000 nm
• Output – 1x NO/NC potential free contacts for fire
• Quiescent Current- less than 15Ma (IH153-FP)  less than 40Ma ( IH153-AP)
• Alarm Current- less than 80Ma (IH153-FP)  less than 100Ma ( IH153-AP)
• Fire Indication – RED LED
• Normal Indication – Flickering GREEN LED
• Air Purging – 3 to 7 bar
• IP Rating – IP67
• External Earthing -2 nos.
• Material – Cast Aluminium LM6
• Cable Entries – Ύ ET – 03
• Fasteners – SS304
• Operating Temperature - -40 to +60C

 

PRODUCT CONFORMS TO REQUIREMENTS OF NFPA72 AND IS-2189.        

 

                                                              
The information provided on this data sheet is accurate at time of going to print. In the interests of improving quality and design, PROLINE PROTECTION SYSTEMS LIMITED reserve the right to amend specifications without prior notice.


                                                               Edited version. 08.07


               Registered Office – Kings Worthy House, Court Road, Kings Worthy, Winchester, Hampshire. SO 23 7QA  U. K.
                              Registered in England – Number  4421495         V.A.T. Registration Number – GB 799 9244 45

 

 

 

 

About Contact Send us an Enquiry Linear Heat Detection General Linear Heat Detection Products Linear Heat - Fixings/Supports Linear Heat - Junction Boxes Linear Heat Detection Applications Linear Detection - Design Newsheets Consultant Specification FAQ's Product Approvals Speciality Cables Beam Detectors Flame Detectors Aspirated Smoke Detector Moisture Detection Stop Press Terms and Conditions Payment Terms